 "id": "colombia-sgc-geociencias",
 "country": "Colombia",
 "language": "Spanish",
 "convention": "IEC-style (Colombian practice)",
 "text_layer": true,
 "quality": "clean AutoCAD vector export, colour lines, dense; labels partly text, ratings drawn as graphics",
 "buyer": "Servicio Geológico Colombiano with Universidad Nacional de Colombia (Convenio 12 de 2015)",
 "project": "Centro de Excelencia en Geociencias, Bogotá, Bloque 1 (design files published as pre-contract documents, V4 30 May 2018)",
 "drawing": "U-B1-1_Diagrama_Unifilar_General_Bloque1.pdf, page 1 (plano 01, U-B1-1, Diagrama unifilar general Bloque 1)",
 "read_by": "Mavlon, read from the drawing with AI help before any run, November 2026",
 "checks": [
  [
   "MV cell count",
   "14 SF6 cells (C1 to C14) in the medium-voltage room (Cuarto de media tensión)"
  ],
  [
   "MV service voltage",
   "11.4 kV (rated 15 kV) per the CT/VT data tables"
  ],
  [
   "MV supply",
   "network operator connection point, 3x240 mm² Al 15 kV XLPE"
  ],
  [
   "C1",
   "incoming cell (entrada)"
  ],
  [
   "C2",
   "outgoing cell (salida), marked SALIDA: LIBRE (spare)"
  ],
  [
   "C3",
   "outgoing cell for the project (salida proyecto)"
  ],
  [
   "C4",
   "riser cell (remonte)"
  ],
  [
   "C5",
   "outgoing cell to common services (servicios comunes)"
  ],
  [
   "C6",
   "outgoing cell to Universidad Nacional (U.N.)"
  ],
  [
   "C7",
   "metering cell for SGC, entry and exit by busbars, with kWh/kVArh meter"
  ],
  [
   "C8",
   "protection cell, HH fuses 63 A, for transformer 1 (SGC, common services)"
  ],
  [
   "C9",
   "protection cell, HH fuses 63 A, for transformer 2 (data center)"
  ],
  [
   "C10",
   "outgoing cell to substation 2 (Bloque 2-3 SGC)"
  ],
  [
   "C11",
   "metering cell for U.N., cable entry and busbar exit, with meter"
  ],
  [
   "C12",
   "protection cell, HH fuses 40 A, for transformer 3 (U.N.)"
  ],
  [
   "C13",
   "metering cell for SGC, cable entry and busbar exit, with meter"
  ],
  [
   "C14",
   "protection cell, HH fuses 25 A, for transformer 4 (SGC, Bloque 1)"
  ],
  [
   "Metering cells",
   "3: C7, C11, C13 (one per owner)"
  ],
  [
   "Protection cells and fuses",
   "4: C8 63 A, C9 63 A, C12 40 A, C14 25 A"
  ],
  [
   "E1 transformer",
   "300 kVA, 11400/208 V, dry type class H, 60 Hz Dy5, In 832.72 A, Icc 13.9 kA, Uz 6%, common services, flexible Al busbar 1000 A"
  ],
  [
   "E2 transformer",
   "800 kVA, 11400/208 V, dry type class H, Dy5, In 2222.2 A, Icc 22 kA, Uz 6%, data center, flexible Cu busbar 1600 A"
  ],
  [
   "E3 transformer",
   "300 kVA, 11400/208 V, dry type class H, Dy5, In 832.72 A, Icc 13.9 kA, Uz 6%, Universidad Nacional, flexible Al busbar 1000 A"
  ],
  [
   "E4 transformer",
   "1000 kVA, 11400/208 V, dry type class H, Dy5, In 2775.72 A, Icc 46.3 kA, Uz 6%, Bloque 1 SGC, flexible Al busbar 4000 A"
  ],
  [
   "Surge protection",
   "DPS 12 kV 10 kA at each transformer"
  ],
  [
   "Generator E6",
   "1600 kVA effective at Bogotá altitude, 440 V, 3x3000 A breaker, Icc ≥ 50 kA, 3200 A flexible Al busbar"
  ],
  [
   "LV-LV transformer E12",
   "1600 kVA, 440 V / 208 V, dry type, 6000 A busbar"
  ],
  [
   "Generator board E13",
   "installed load 1600 kVA; 3x1000 A, 3x1000 A, 3x3500 A outgoing and a 3x6000 A main, Icc > 50 kA"
  ],
  [
   "Busways",
   "electrobarras: 3200 A Al (E6 to E11 to E12), 6000 A Al, plus 4000 A, 1250 A and 630 A risers, all to standard ET-126"
  ],
  [
   "Transfer boards",
   "E8 (common services), E16 (Universidad Nacional), E18 (transfer board 3)"
  ],
  [
   "Capacitor banks",
   "E9, E17, E19"
  ],
  [
   "Fire pump",
   "E14 fire pump transfer, E15 fire pump board, 200 HP pump plus jockey pump, certified controller"
  ],
  [
   "Equipment E5 and E7",
   "not used: the equipment list skips from E4 to E6 and from E6 to E8"
  ],
  [
   "Connection to Bloque 2",
   "feeder 'VA A SUBESTACIÓN BLOQUE 2' from C10"
  ]
 ]
}