 "id": "denmark-dtu-lyngby",
 "country": "Denmark",
 "language": "Danish",
 "convention": "IEC",
 "text_layer": false,
 "quality": "low-resolution raster (about 100 ppi) pasted into a Word document; small labels barely legible",
 "buyer": "Technical University of Denmark (DTU) Campus Service",
 "project": "450 El - Bilag 01, Information om DTUs El-infrastruktur, v1.1, 17.10.2018 (buyer's technical standard; not a tender)",
 "drawing": "DTU_450_El_Bilag_01_El-infrastruktur.pdf, page 7 (Figur 2, Transformerstation IV ved bygning 223); campus network on page 5",
 "read_by": "Mavlon, read from the drawing with AI help before any run, November 2026",
 "checks": [
  [
   "Station",
   "Transformerstation IV by building 223"
  ],
  [
   "MV board",
   "10 kV, 3~50 Hz, 4 panels (1 to 4); RM6 type per the text"
  ],
  [
   "Panel 1",
   "two load-break switches with earthing switches (A12.3 and A12.1) on the incoming and outgoing 10 kV radial, cables 3x240 PEX-Al"
  ],
  [
   "Panels 2 and 3",
   "circuit breakers with VIP 30 relays feeding transformers TR1 and TR2, cables 3x50"
  ],
  [
   "Panel 4",
   "circuit breaker with 63 A fuse and VIP 30 relay feeding transformer TR3, with an earthing switch"
  ],
  [
   "Transformers",
   "3 x 800 kVA, 10/0.4 kV"
  ],
  [
   "LV incomers",
   "TR1, TR2 and TR3 breakers with ammeters and voltmeters; TR1/TR2 cables 3x800+400"
  ],
  [
   "LV couplers",
   "a coupler between the TR1 and TR2 sections and a 1600 A coupler before the TR3 section"
  ],
  [
   "LV outgoing feeders",
   "about 30, rated 200 A, 350 A or 400 A, to buildings 222 to 229, a tunnel board, a sewage pump station and spares (disp. afbrydere)"
  ],
  [
   "LV feeder cables",
   "sizes from 3x120+60 to 3x240+120 and 4x240, with some Al cables 3x185 and 3x240"
  ],
  [
   "Design rule",
   "the text says every station has at least two transformers, and the 10 kV radial loops on through a load-break panel"
  ]
 ]
}