 "id": "germany-leipzig-lvb",
 "country": "Germany",
 "language": "German",
 "convention": "IEC (DIN/VDE)",
 "text_layer": false,
 "quality": "image-only PDF of a clean CAD print",
 "buyer": "Leipziger Verkehrsbetriebe (LVB) GmbH",
 "project": "Umstellung des GUWs Mockau auf 750 V (tender 2026-RL-27-02, lot VE 02)",
 "drawing": "B_20260902_90053_VE02_Anlagen_Pläne/01_03_01_0_6_1_250519_UeSchPlan.pdf (also inside the ZIP), page 1 (sheet 01_03_01, Übersichtsschaltplan, SIGNON Deutschland, 12.05.2024)",
 "read_by": "Mavlon, read from the drawing with AI help before any run, November 2026",
 "checks": [
  [
   "MV panel count",
   "8 (K01 to K08)"
  ],
  [
   "MV switchgear type",
   "gas-insulated, SF6-free (BlueGIS 24 kV), except K04 which is air-insulated"
  ],
  [
   "MV operating voltage",
   "10 kV network (incomer labels 'Mittelspannung 10 kV Netz LVB'; transformer primaries 10 kV)"
  ],
  [
   "K01",
   "Einspeisung 1 (incoming feeder 1)"
  ],
  [
   "K02",
   "Einspeisung 2 (incoming feeder 2)"
  ],
  [
   "K03",
   "Übergabe (handover) with LVB voltage measurement"
  ],
  [
   "K04",
   "Messung: air-insulated metering panel, 3 CTs and 3 VTs, to the grid operator's meter cabinet (kWh, kvarh)"
  ],
  [
   "K05",
   "Kabelanschluss (cable connection panel)"
  ],
  [
   "K06",
   "feeder to rectifier transformer 1 (GR-Transformator 1)"
  ],
  [
   "K07",
   "feeder to rectifier transformer 2 (GR-Transformator 2)"
  ],
  [
   "K08",
   "feeder to auxiliary transformer (EB-Transformator)"
  ],
  [
   "Switching device K01, K02, K03, K06, K07",
   "motor-operated circuit breaker"
  ],
  [
   "Switching device K08",
   "switch-disconnector with HV fuses"
  ],
  [
   "Current marked on switching panels",
   "630 A (K01, K02, K03, K06, K07, K08)"
  ],
  [
   "Protection relay",
   "7SJ80 on K01, K02, K03, K06, K07"
  ],
  [
   "Incomer changeover",
   "automatic changeover via PLC (Umschaltautomatik über SPS) on K01 and K02"
  ],
  [
   "Incoming cables",
   "3x1x240 mm² NA2XS(F)2Y on K01 and K02"
  ],
  [
   "Transformer feeder cables",
   "3x1x95 mm² NA2XS2Y on K06, K07, K08"
  ],
  [
   "GR-Trafo 1",
   "1860 kVA, Yy0"
  ],
  [
   "GR-Trafo 2",
   "1860 kVA, Dy5"
  ],
  [
   "GR-Trafo secondary voltages",
   "3AC 0.511 kV and 3AC 0.666 kV"
  ],
  [
   "EB-Trafo",
   "63 kVA, Dyn5, 10 kV / 3AC 0.4 kV"
  ],
  [
   "ON-Trenntrafo",
   "25 kVA, Dyn5 (local-grid isolating transformer)"
  ],
  [
   "DC system voltage",
   "750 V (title block)"
  ],
  [
   "Rectifiers",
   "2 (Gleichrichter 1 and 2), 3000 A"
  ],
  [
   "Track feeder panels",
   "6 (Strecke 1 to 6)"
  ],
  [
   "Other DC panels",
   "Rückleiterfeld (return), Einspeisung (DC infeed), Streckenersatz/Umgehungszelle (bypass)"
  ],
  [
   "Return branches",
   "6 (RZ1 to RZ6)"
  ],
  [
   "DC cell ratings",
   "DC fast breaker 2600 A, bypass disconnector 2600 A, cable disconnector 1250 A"
  ],
  [
   "Track feeder cables",
   "2 x NA2XS(F)2Y 500 mm² Al per feeder"
  ],
  [
   "Auxiliary distribution NE1",
   "AC 400/230 V 50 Hz"
  ],
  [
   "Battery NQ1",
   "battery and charger, DC 110 V"
  ],
  [
   "Low-voltage utility supply",
   "VNB 3AC 0.4 kV via HAK and the grid operator's meter"
  ]
 ]
}