 "id": "india-bhel-rasra-lt-switchgear",
 "country": "India",
 "language": "English (Hindi/English title block)",
 "convention": "IEC-style graphics with ANSI relay device numbers",
 "text_layer": false,
 "quality": "clean CAD rasterised to a 1-bit image, A0 sheet rotated; dense",
 "buyer": "BHEL Transmission Projects Division (end customer UP Power Transmission Corporation)",
 "project": "LT switchgear (AC and DC distribution boards) for the 400/220/132 kV GIS substation at Rasra, Ballia, spec TB-404-316-026",
 "drawing": "BHEL_TB-404-316-026_LT_Switchgear_Spec_SLD_BOQ_Rasra_Ballia.pdf, page 7 (drawing TB-0-404-316-026 Rev 00)",
 "read_by": "Mavlon, read from the drawing with AI help before any run, November 2026",
 "checks": [
  [
   "Boards on the sheet",
   "415V main switch board (1A), 415V AC distribution board (2A), 415V MLDB (3A), 415V colony lighting DB (4A), 415V ELDB (5A), 220V DC distribution boards 1 and 2 (1D, 2D), 48V DC distribution boards 1 and 2 (3D, 4D)"
  ],
  [
   "Main switch board bus",
   "415 V, 3 phase, 4 wire, 1250 A, 25 kA for 1 s, two buses (bus 1 and bus 2)"
  ],
  [
   "Main switch board incomers",
   "2 incomers, each 1250 A ACB"
  ],
  [
   "Bus coupler",
   "1250 A ACB between bus 1 and bus 2"
  ],
  [
   "Incomer 1 source",
   "from SEB supply through an outdoor LT substation transformer"
  ],
  [
   "Incomer 2 source",
   "from the tertiary of a 500 MVA 400/220/33 kV transformer through an outdoor LT substation transformer"
  ],
  [
   "LT transformers",
   "2 x 630 kVA, 33 kV / 0.415 kV, Dyn1, 5% Z, outdoor, with neutral CT (NCT)"
  ],
  [
   "Incomer cables",
   "(3x2+1) x 1C x 630 sq mm on each incomer"
  ],
  [
   "Incomer CTs",
   "1250/1 A class 1 (meter) and two 1250/1 A 5P15 (protection)"
  ],
  [
   "Incomer protection",
   "51, 51N, 50N and 64 (restricted earth fault), multifunction meter MFM"
  ],
  [
   "Bus voltage relays",
   "27X, 27A, 27B and 2 on each bus, with 415/√3 / 110/√3 V PT"
  ],
  [
   "DG set",
   "415 V, 250 kVA DG set through a 415 V AMF panel"
  ],
  [
   "DG incomer",
   "4-pole ACB 630 A on the AC distribution board, with relays 87, 95 and 51 and 400/1 A CTs"
  ],
  [
   "DG cables",
   "2 x 3½C x 300 sq mm"
  ],
  [
   "AC distribution board (2A)",
   "415 V, 3 phase, 4 wire, 800 A, 20 kA for 1 s, two buses with coupler"
  ],
  [
   "ACDB incomers",
   "800 A ACBs fed from the main switch board"
  ],
  [
   "MLDB (3A)",
   "415 V, 3 phase, 4 wire, 500 A bus, two 150 kVA Dyn1 415/415 V lighting transformers"
  ],
  [
   "Colony lighting DB (4A)",
   "415 V, 3 phase, 4 wire, 400 A bus, two 150 kVA Dyn1 415/415 V lighting transformers"
  ],
  [
   "ELDB (5A)",
   "415 V, 3 phase, 4 wire, 200 A bus, one 50 kVA Dyn1 415/415 V lighting transformer"
  ],
  [
   "Main switch board outgoing",
   "module ratings include 800 A ACB, 630 A ACB, 500 A and 400 A feeders"
  ],
  [
   "220V DC distribution boards",
   "2 boards (1D, 2D), 220 V, 400 A, 20 kA for 1 s (DC), each with a DC module and battery"
  ],
  [
   "48V DC distribution boards",
   "2 boards (3D, 4D), 48 V, 400 A, 20 kA for 1 s (DC), each with a DC module and battery"
  ],
  [
   "Battery chargers",
   "chargers per DC board with float and boost, fed from the ACDB"
  ],
  [
   "Paralleling rule",
   "note 1: no two AC sources shall be paralleled at any stage"
  ],
  [
   "Relay legend",
   "50N, 50, 51, 50/51, 2, 27X, 27, 59, 51V, 87, 95, 64 and 96 are defined in the legend"
  ],
  [
   "Signal tables",
   "tables of analog signals, potential-free contacts and commands for remote indication (main switch board, ACDB, DC boards, chargers, LT transformers, DG set)"
  ]
 ]
}