 "id": "india-scan-bhel-powergrid-ss19",
 "country": "India",
 "language": "English (Hindi stamps and title block)",
 "convention": "IEC-style graphics with ANSI device numbers (52, 89, 89E)",
 "text_layer": false,
 "quality": "real paper scan at 150 ppi: pink tint, fold lines, red hand markups, approval rubber stamp; small device text marginal",
 "buyer": "BHEL Transmission Projects Division (end customer POWERGRID)",
 "project": "Substation Package SS-19, extension of 400 kV Champa substation under WRSS-20 (spec TB-408-510-010)",
 "drawing": "BHEL_TB-408-510-010_PowerGrid_SS-19_SAS_Spec_with_scanned_SLDs.pdf, page 72 (drawing TB-408-510-C01 Rev 01, Single line diagram for extn. of 400 kV Champa S/S)",
 "scope_note": "400 kV switchyard (not MV/LV switchgear); included as the hard-scan test",
 "read_by": "Mavlon, read from the drawing with AI help before any run, November 2026",
 "checks": [
  [
   "Voltage level",
   "400 kV switchyard"
  ],
  [
   "Main buses",
   "400 kV main bus I and main bus II, each 50 kA for 1 s, 10 in. IPS aluminium tube"
  ],
  [
   "Present scope",
   "one 125 MVAR 400 kV bus reactor bay (Detail A), bay 432"
  ],
  [
   "Present scope equipment chain",
   "432-BR reactor, 432-LA surge arrester, 432-89LE and 432-89L isolators, 432-89A and 432-89E, 432-CT, 432-52 breaker"
  ],
  [
   "BOQ item 1",
   "125 MVAR 400 kV 3-phase bus reactor, quantity 1, not in BHEL scope of supply"
  ],
  [
   "BOQ item 2",
   "400 kV 3150 A 50 kA for 1 s 3-phase circuit breaker without closing resistor and with CSD, quantity 1"
  ],
  [
   "BOQ item 3",
   "400 kV 3150 A 50 kA for 1 s 3-phase horizontal double break isolator with 1 earth switch, quantity 2"
  ],
  [
   "BOQ item 4",
   "400 kV 3000 A 50 kA for 1 s 1-phase current transformer with 120% extended current rating, quantity 3"
  ],
  [
   "BOQ item 5",
   "336 kV 1-phase surge arrester, quantity 3"
  ],
  [
   "System voltage",
   "400 kV operating, 420 kV maximum, 50 Hz"
  ],
  [
   "Insulation levels",
   "1550 kVp lightning impulse, 1050 kVp switching impulse, 630 kV power frequency"
  ],
  [
   "Fault level",
   "50 kA for 1 s"
  ],
  [
   "Creepage",
   "10500 mm minimum creepage distance"
  ],
  [
   "CT details",
   "420 kV, 3000 A, 6 cores, all 3000-2000-500/1"
  ],
  [
   "CT core purposes",
   "1 bus diff check (PX), 2 bus diff main (PX), 3 and 4 metering (0.2S, 20 VA), 5 reactor backup (PX), 6 reactor diff (PX)"
  ],
  [
   "Existing bays named",
   "Lanco 1 to 4, KSK 1 to 4, Lara I and II, MB Power 1 and 2 (future), AT#1 to AT#6, 80 MVAR bus reactor, HVDC poles 1 to 4, AC filters 4 to 6, reactive compensation (future)"
  ],
  [
   "Hand markups",
   "red additions mark AT#4, AT#5 and AT#6 as 765/400 kV ATs, bay numbers 477, 478 and 479 written in, several future bays crossed out"
  ],
  [
   "Approval stamp",
   "POWERGRID approval stamp with 'Cat I*' handwritten, dated 25.11.19"
  ],
  [
   "Revision",
   "Rev 00 dated 13.11.19, drawing revised per POWERGRID comments (letter dated 01.11.19); drawn 28.09.19"
  ],
  [
   "NOA",
   "CC-CS/901-WR2/SS-3931/3/G3/NOA-I/8864 & 8865 dated 29.07.19"
  ]
 ]
}