 "id": "switzerland-oberegg-ts-haggen",
 "country": "Switzerland",
 "language": "German",
 "convention": "IEC",
 "text_layer": "partial",
 "quality": "clean vector export, page rotated; field names and relay types are text, ratings are outlines",
 "buyer": "Elektra Oberegg (local utility), drawn by EVU-Beratung AG",
 "project": "Trafostation Haggen, Prinzipschema (plan 212956/5.1, 7.2.2017); published in the Kanton Appenzell Innerrhoden public consultation for the Honegg wind turbine, 2024; not a tender",
 "drawing": "Beilage_28_Elektra_Oberegg_Prinzipschema_Trafostation_Haggen.pdf, page 1",
 "read_by": "Mavlon, read from the drawing with AI help before any run, November 2026",
 "checks": [
  [
   "Voltage",
   "20 kV single busbar"
  ],
  [
   "Panel count",
   "4 panels (Feld 1 to Feld 4)"
  ],
  [
   "Feld 1",
   "Messfeld (metering panel): CT 30/5 A, VT 20 kV/100 V, to the metering board (Messtableau)"
  ],
  [
   "Feld 2",
   "T4k, circuit breaker panel to the wind power plant (Windkraftwerk M)"
  ],
  [
   "Feld 3",
   "T4k, circuit breaker panel to TS St. Anton"
  ],
  [
   "Feld 4",
   "T4t, circuit breaker panel to a 250 kVA transformer"
  ],
  [
   "Breakers",
   "spring-charged (F.-Speicher) with ON/OFF control and earthing switch, on Felder 2, 3 and 4"
  ],
  [
   "Relays",
   "Siemens 7SJ8011 on Felder 2, 3 and 4"
  ],
  [
   "CTs",
   "10/1 A on Feld 4 (In 7.22 A); 200-400/1 A on Felder 2 and 3"
  ],
  [
   "Surge arresters",
   "on Felder 2 and 3"
  ],
  [
   "Second outgoing",
   "Windkraftwerk 1 connected off the bus beside the metering panel"
  ],
  [
   "Voltage indicators",
   "capacitive voltage indicators on each breaker panel"
  ]
 ]
}