 "id": "us-saws-mv-switchgear",
 "country": "United States",
 "language": "English",
 "convention": "ANSI/IEEE with device numbers",
 "text_layer": false,
 "quality": "CAD drawing rasterised at 150 ppi (crisp, no text layer)",
 "buyer": "San Antonio Water System (engineer Tetra Tech)",
 "project": "IFB 18-18099, early procurement of medium voltage switchgear, Central Water Integration Pipeline (2018)",
 "drawing": "SAWS_18-18099_MV_Switchgear_Bid_Set_specs_and_drawings.pdf, page 105 (sheet E-1007, Main switchgear one-line diagram)",
 "read_by": "Mavlon, read from the drawing with AI help before any run, November 2026",
 "checks": [
  [
   "Lineup",
   "Outdoor main switchgear MV-SWGR-1, outdoor walk-in (note 1), 5 kV"
  ],
  [
   "Sources",
   "two CPS Energy normal feeds from power poles PP1 and PP2"
  ],
  [
   "Utility transformers",
   "TX-1 and TX-2, 3000 kVA, 34.5 kV to 4160 V, power company pad-mounted (note 3)"
  ],
  [
   "Main breakers",
   "MB-1 and MB-2: 1200 A, 5 kV, 95 kV BIL, 31.5 kA rated"
  ],
  [
   "Tie breaker",
   "MB-3 (tie): 1200 A, 5 kV, 95 kV BIL, 31.5 kA rated"
  ],
  [
   "Key interlock",
   "Kirk key symbol (K) between the mains and the tie"
  ],
  [
   "Main bus",
   "1200 A bus, 5 kV, on both sides of the tie"
  ],
  [
   "Feeder breakers",
   "two, both labelled CB-1: 600 A, 5 kV, 95 kV BIL, 31.5 kA, to MV-MCC-A and MV-MCC-B"
  ],
  [
   "Feeder label inconsistency",
   "both feeder breakers carry the same label CB-1"
  ],
  [
   "Spaces",
   "three spaces shown on the bus (one left, two right)"
  ],
  [
   "Overcurrent relays",
   "GE Multilin 850 (device 51) on mains, tie and feeders"
  ],
  [
   "Lockout relays",
   "device 86 on each breaker"
  ],
  [
   "Voltage relays",
   "27/47 and 27/47X on each incoming side"
  ],
  [
   "Meters",
   "Multilin PQM2 (A, PF, V, W) on each incoming side"
  ],
  [
   "Current transformers",
   "3 CTs 800/5 on each main and on the tie; CT(3) on each feeder"
  ],
  [
   "Potential transformers",
   "3 PTs (L-L) 4800/120 V on each incoming side"
  ],
  [
   "Control power transformers",
   "3 kVA minimum, 2400 V to 120 V, one per side, for heaters and breaker controls; CPT throw-over (note 10)"
  ],
  [
   "Surge protection",
   "lightning arrester on each incoming line, with a contact for SCADA monitoring"
  ],
  [
   "Incoming cables",
   "4 in. conduit, 3 x 750 kcmil (5 kV, MV-105), 250 kcmil neutral (600 V) and a 4 in. spare conduit"
  ],
  [
   "Feeder cables",
   "4 in. conduit, 3 x 750 kcmil (5 kV, MV-105), 250 kcmil ground (600 V) and a 4 in. spare conduit"
  ],
  [
   "Utility metering",
   "CPS Energy metering in the transformer secondary compartment (notes 12 and 13)"
  ],
  [
   "Racking",
   "breakers remotely racked by an internal racking mechanism; one racking device"
  ],
  [
   "Elevation sections",
   "6 sections, 18 ft 0 in long, 3 ft 0 in each"
  ],
  [
   "Elevation lower row",
   "MV-MCC-A feeder, main, tie, tie aux, main, MV-MCC-B feeder"
  ],
  [
   "Elevation upper row",
   "future feeder, CPT/PTs, bus PTs, bus PTs, CPT/PTs, future feeder"
  ],
  [
   "Drawing inconsistency",
   "bus PTs appear on the elevation but not on the one-line"
  ],
  [
   "Enclosure",
   "steel, walls bolted, roof welded, exterior painted ANSI 61 gray, stainless hardware (type 316)"
  ],
  [
   "Communications",
   "E-NET connections from relays and meters to the Ethernet network switch; to PLC 01-CP-01"
  ]
 ]
}