Busbar Calculator: size, ampacity, weight and cost for a switchboard lineup
Enter the current. Get the bars per phase at a published current density, the single-bar ampacity from the Copper Development Association table, and the weight and metal cost of the bus for the whole lineup.
| Run | Bars | Each | Bar total | Weight |
|---|---|---|---|---|
| Main horizontal bus, phases | 3 × (2 × 1/4 × 4 in) | 144.0 in | 72.0 ft | 278.2 lb |
| Main horizontal bus, full neutral | 1 × (2 × 1/4 × 4 in) | 144.0 in | 24.0 ft | 92.7 lb |
| Vertical section bus, phases | 12 × (1 × 1/4 × 3 1/2 in) | 72.0 in | 72.0 ft | 243.4 lb |
| Vertical section bus, full neutral | 4 × (1 × 1/4 × 3 1/2 in) | 72.0 in | 24.0 ft | 81.1 lb |
| Run-backs to devices, phases | 24 × (1 × 1/4 × 2 in) | 18.0 in | 36.0 ft | 69.6 lb |
| Ground bus | 1 × (1 × 1/4 × 2 in) | 144.0 in | 12.0 ft | 23.2 lb |
| Total | 240.0 ft | 788.3 lb |
How to calculate busbar size for a panel or switchboard
The busbar calculation formula is one division: area = current ÷ density, where density is the current each square inch of bar is allowed to carry. Makers of UL 891 switchboards offer two kinds of bus. One is sized by a heat-rise test on the finished design. The other is density rated: no more than 1,000 A for every square inch of copper, or 750 A for every square inch of aluminum. The density rule needs no test, which is why it is the one a calculator can do honestly.
Worked example, the one the tool opens with: a 2,000 A copper main bus needs 2,000 ÷ 1,000 = 2.0 sq in per phase. A 1/4 by 4 inch bar is exactly one square inch, so that is two 1/4 × 4 bars per phase. If your enclosure only takes a 3 inch bar, set the widest bar to 3 and the tool moves to three bars. Leave bar size on Auto and it picks the narrowest standard bar that carries the current. Change the density field if your own tested design runs at a different figure.
Busbar ampacity: the table and the density rule give different numbers
Look up that same 1/4 × 4 bar in the Copper Development Association table and it says 1,250 A at a 30°C rise, 1,700 A at 50°C and 1,950 A at 65°C. The density rule says 1,000 A. Both are right, for different situations. The table is for one bar, on edge, in open air indoors at 40°C, free to shed heat from both faces. A switchboard bus is several bars stacked inside a steel box next to breakers that make their own heat.
So the tool shows both, labelled. Use the table to compare bar shapes and to see how much a wide thin bar gains over a thick narrow one. Use the density rating, or your own tested design, for the bus you are actually quoting. The table values do not multiply when you stack bars, and the tool will not multiply them for you.
Copper busbar weight calculation
Weight is cross-section times length times the metal's density. Copper is 0.322 lb per cubic inch, which works out to 3.86 lb per foot for every square inch of bar. Aluminum bus conductor is about 0.0975 lb per cubic inch, or 1.17 lb per foot per square inch.
That gives the copper against aluminum trade in two numbers. Aluminum needs a third more cross-section to carry the same current at its 750 A density, so the bars are bigger and the enclosure has to hold them. But the aluminum bus weighs only about 40 percent of the copper one. Which is cheaper depends on your bar prices, which is why the price field is yours to fill in and the tool does not guess at it.
Where the bar in a lineup actually goes
Sizing one bus is the easy half. The quote needs the total, and the total is a count:
- Main horizontal bus: the full width of the lineup, three phases, plus the neutral if there is one.
- Vertical bus: one set in each section that feeds devices, usually at a lower rating than the main bus.
- Run-backs: the short bars from the vertical bus to each breaker or switch.
- Ground bus: one bar along the bottom, full width.
The opening example is a four section, 12 foot lineup: 2,000 A main bus with a full neutral, 800 A vertical bus in every section, eight 400 A run-backs and a ground bus. It comes to 788 lb of copper in 240 feet of bar. The main bus is 371 lb of that. The vertical bus is 325 lb, nearly as much, which is easy to miss if you size only the main bus. We worked this example by hand before publishing the tool, and it agrees with the weights printed in the Copper Development Association table to within a tenth of one percent.
What this busbar calculator does not check
A bus that carries the current still has to survive a fault. Short-circuit bracing, support spacing and the withstand rating come from the tested design, not from cross-section. Neither does this tool cover temperature rise inside your enclosure, joints and plating, or what your listing allows. Treat the result as the takeoff for a quote and a check on a design, not as the design.
And the bus is only as right as the rating you start from. On one public switchgear specification we read, page 9 gave two fault ratings that could not both be true, and the cheaper reading and the safer reading were different lineups. That kind of problem is in the document, not in the arithmetic. We wrote up what twelve real specifications ask for in how to quote switchgear.
Sources. Bar sizes, weights, resistance and single-bar ampacities: Copper Development Association Inc., Table 1, Ampacities of Copper No. 110 Busbars. Density ratings of 1,000 A per square inch for copper and 750 for aluminum: as published by switchboard makers for UL 891 gear, for example this product sheet. Found a mistake? Write to atishay@mavlon.co and we will fix it.
The bus is one line of a switchgear quote. The specification is the rest.
Mavlon reads the customer's specification and drawings, ties every requirement that changes the price to its page, flags the ones that disagree, and drafts the quote in your own pricing rules.
Book a DemoShown on a public switchgear specification